01Enter one battery ratingUse the voltage and Ah printed on one battery or module.
02Count series batteriesSeries adds voltage while Ah stays the same. Two 12V 200Ah batteries in series become 24V 200Ah.
03Count parallel stringsParallel adds Ah. Two identical 24V 200Ah strings in parallel become 24V 400Ah.
04Choose usable depthLead-acid batteries are usually not sized around 100% discharge. Lithium systems often allow a larger usable share, subject to the manufacturer/BMS.
05Account for battery healthOlder or damaged batteries may deliver much less than their nameplate Ah.
06Enter the real AC loadUse the combined running watts of the equipment expected to stay on during backup.
07Include inverter lossesThe inverter consumes energy while converting DC battery energy to AC power.
08Check high-power loadsPumps, compressors, fridges and AC units can have starting surges that affect inverter suitability even when average runtime looks acceptable.
09Verify on siteAfter installation, compare calculated runtime with actual discharge behavior and battery/inverter monitoring data.